Forane® R-22 RetrofitsRetrofit SolutionsArkema recommends Forane® 407C, 407A, and 427A as retrofit options for many R-22 applications. All are SNAP approved. When reviewing the various retrofit considerations – GWP, capacity, efficiency, operating pressures, flow rates – you will find that these products represent some of the closest overall performance matches to R-22 available on the market today. R-407C has the closest capacity to R-22 for air conditioning, while R-407A offers performance similar to R-22 in supermarket refrigeration. R-427A is a hybrid blend that mirrors R-22's operating pressures, allowing it to be used in a wider range of systems. Forane® 404A and 507A can also be used to retrofit some R-22 refrigeration systems. However, these products typically require additional system modifications to achieve similar performance. For further information on retrofitting your existing system, please use our Retrofit Data Sheet. Retrofit Solutions: | Forane® 22 | Forane® 407C | Forane® 427A | Forane® 407A |
|---|
| Primary Usage | All R-22 Systems | Air Conditioning | General Purpose R-22 Retrofit | Commercial Refrigeration | | Application Range | All R-22 Systems | AC → MT (DX) New & Retrofit | AC → LT (DX) Retrofit Only | MT → LT (DX) New & Retrofit | Composition (Weight %) | 100% R-22 | 23% R-32 25% R-125 52% R-134a | 15% R-32 25% R-125 10% R-143a 50% R-134a | 20% R-32 40% R-125 40% R-134a | | GWP (100 year) | 1,810 | 1,774 | 2,138 | 2,107 | Normal Boiling Point (ºF) | -41 | -47 | -45 | -49 | Critical Temperature (ºF) | 205 | 187 | 186 | 180 | Capacity (Relative to R-22) | Same | Similar (AC) | Slightly Lower | Similar (MT → LT) | Flow Rates (Relative to R-22) | Same | Similar | Similar | Slightly Higher | | TXV Change-out | N/A | NO | NO | NO | Recommended Lubricant | MO or AB | POE | Partial POE MO* or AB* *With Oil Separator | POE | Charge Ratio (Relative to R-22) | 100% | 90-95% | 95-100% | 95-100% | Discharge Pressure (Relative to R-22) | Same | 15-25 psi Higher | 0-10 psi Higher | 25-35 psi Higher | Discharge Temperature (Relative to R-22) | Same | 10-15 ºF Lower | 25-45 ºF Lower | 20-35 ºF Lower |
LT=Low Temperature MT=Medium Temperature * A lubricant change may not be required, but POE is always recommended for optimal performance. Retrofit Procedure for R-22: R-407C, R-407A, or R-427A- Establish baseline performance. Note the oil type in use and any system operating data (if system is operating properly). Check for existing leaks and identify any needed repairs.
- Recover the existing refrigerant charge (DO NOT vent to atmosphere). Weigh the amount of refrigerant removed.
- Perform any repairs identified in step 1 and fix any leaks.
- Replace the filter-drier and, if necessary, elastomeric seals (O-rings, Schrader valves, etc.). Verify the condition of the system oil; replace, if necessary.
- POE is the recommended lubricant for R-407C, R-407A, and R-427A.
- For R-427A, if an oil separator is in use and reliable oil return with R-22 is established, replacement of the original mineral oil/alkylbenzene may not be needed (skip to step 7). Otherwise, proceed to next step below.
- Drain the existing mineral oil or alkylbenzene from the compressor sump, suction line accumulators, etc... Record the amount of oil removed.
- Add an equivalent amount of OEM-recommended POE oil. In some cases, additional oil flushes may be required to meet OEM recommendations. With R-427A, multiple oil flushes are typically not required.
- Evacuate the system (less than 500 microns) and ensure it maintains a vacuum. If vacuum is lost, it may indicate that leaks are present in the system.
- Charge the system with the new refrigerant as liquid only from cylinder. The charge weight for
R-407C and R-407A/R-427A should be approximately 90-95% and 95-100% of the weight of R-22, respectively. - Adjust TXV set-point and/or refrigerant charge to achieve the desired superheat. Low side pressure control settings may also need to be adjusted.
- If possible, monitor the oil level in the compressor. Adjust oil amount as necessary to attain normal operating level (mid-sight glass). Perform additional flushes only as required.
- Label system clearly, indicating the type and amounts of system refrigerant and oil.
|